10kV High Voltage Switchgear, Power Cable and Transformer Test Report
Line name: #1 transformer ring network outlet cabinet - transformer Test date: 202507.29
1. Nameplate parameters Weather: sunny temperature: 30°C Humidity: 45%
| |||
|
|
|
|
|
|
| 20KA |
|
|
| 25041425 |
| |||
| |||
| YJV22-8.7/15 |
| 8.7/15kV |
|
|
|
|
| 2025.7 |
| 1 |
|
| ||
| |||
|
|
|
|
| 2750KVA的 |
|
|
| 2025.7 |
| |
|
| ||
2. Test equipment
|
|
|
|
1 |
| 3125 | 2310250082 |
2 |
| TKJW-240KVA/120kV | 210618 |
3. Insulation resistance test
The main loop insulation resistance test is performed on the high-voltage switchgear, high-voltage cable, and transformer at a voltage level of 2500V.
|
|
|
|
| 5000 | 5000 |
|
| 5000 | 5000 |
|
| 5000 | 5000 |
|
4. AC withstand pressure test
The main loop power frequency withstand voltage follows the IEC60076, IEC60502-2 standards, and the AC withstand voltage test is carried out on the high-voltage switchgear, high-voltage cable and transformer, and the test voltage level is 30.5KV, 1 minute.
|
|
|
|
| 30.5 | 1 |
|
| 30.5 | 1 |
|
| 30.5 | 1 |
|
5. Phase check
|
|
6. Test conclusion:
The test data conforms to the "(GB 50150-2016) Test Standard for the Handover of Electrical Equipment in Electrical Installation Engineering", I EC test standard and manufacturer's technical parameters, and the test is qualified.
Tester: Reviewer: