本说明资料为使用 HQM6100UN 系列控制器时提供快速操作指引,详细请参阅标准使用说明。 This document provides quick operational guidance for using the HQM6100UN series controllers; for detailed information, please refer to the standard user manual.
HQM6100UN 系列有四种型号如下所述:The HQM6100UN series has four models, described as follows:
型号Model
描述Description
HQM6110UN/6110UNCHQM6110UN/6110UNC
用于单机自动化控制。Used for single-machine automation control.
HQM6120UN/6120UNCHQM6120UN/6120UNC
在 HQM6110UN/6110UNC 基础上增加了市电电量监测和市电/发电自动切换控制功能(AMF)。 Enhanced features based on the HQM6110UN/6110UNC include city power consumption monitoring and city power/generation automatic switching control function (AMF).
注 1:HQM6110UNC/6120UNC 具有 RS485 接口,HQM6110UN/6120UN无 RS485 接口。 Note 1: The HQM6110UNC/6120UNC has an RS485 interface, while the HQM6110UN/6120UN does not have an RS485 interface.
注 2:后文均以 HQM6110UNC/6120UNC 为例进行描述。 Note 2: The following descriptions are provided using the HQM6110UNC/6120UNC as an example.
1.按键功能描述1. Key Function Description
0
停机复位链Emergency Stop Chain
In both manual and automatic modes, it can stop the running generator set. In the generator set alarm state, it can reset the alarm of any unit. In the shutdown mode, pressing this button for more than 3 seconds can test whether the panel indicator lights are normal (test light). During shutdown, pressing this button again can quickly shut down.
在手动/自动模式下,均可以使运转中的发电机组停止。
在发电机组报警状态下,可以使任何的序机报警复位。在停机模式下,按下此㴶 3 s 以上,可以测试面板指示灯是否正常(试灯)。
在停机过程中,再次按下此㯈,可快速停机。
在手动/自动模式下,均可以使运转中的发电机组停止。
在发电机组报警状态下,可以使任何的序机报警复位。在停机模式下,按下此㴶 3 s 以上,可以测试面板指示灯是否正常(试灯)。
在停机过程中,再次按下此㯈,可快速停机。| 在手动/自动模式下,均可以使运转中的发电机组停止。 |
| :--- |
| 在发电机组报警状态下,可以使任何的序机报警复位。在停机模式下,按下此㴶 3 s 以上,可以测试面板指示灯是否正常(试灯)。 |
| 在停机过程中,再次按下此㯈,可快速停机。 |
I
开机䋖Start-up Chain
在手动模式或手动试机模式下,按下此琏可以使静止的发电机组开始起动。 In manual mode or manual test mode, pressing this chain can start the startup of a stationary generator set.
gov
手动键Manual input
按下此键,可以将控制噆置于手动模式。Press this key to set the control mode to manual.
@
白动键Automatic key
按下此㵦,可以将控制器置于自动模式。Pressing this key can set the controller to automatic mode.
合分间䭔Switch operation
在手动模式下,按下此綎,可控制开关合分闸。In manual mode, pressing this key can control the switch on and off.
OK
设置/确认键Set / Confirm Key
在参數设置中移动光标及确认设置信息。Move cursor and confirm settings information in parameter settings.
Delta\Delta
上翻增加Up scroll increase
租屏,在參数设置中问上移动光标或增加光标所在位的数字。 Rental screen, move cursor up in parameter settings or increase the number at the cursor position.
下翻/减少Scroll Down / Decrease
翻屏,在参数设置中问下移动光标或减少光标所在位的数字。 Scroll to move the cursor down in parameter settings or decrease the number at the cursor position.
菜单键Menu Key
按下此镁,进入设置菜单,再次按下此键,可返回主界面。 Press this key to enter the settings menu, press it again to return to the main interface.
1)在控制器开机后按目键即可进入菜单界面,选择 1 控制器参数整定如图1: 1)After the controller is powered on, press the "Menu" key to enter the menu interface. Select 1 to adjust the controller parameters, as shown in Figure 1:
2)按 0 K 揵进入參数设置口令输入界面,如图 2 所示;(输入口令" 1234 "可设置配置参数的部分项," 0318 " 2)Press 0 K to enter the parameter setting password input interface, as shown in Figure 2; (Entering password "1234" can set some of the configuration parameters, "0318")
可设置配置參数的所有项。方法见步骤3):All items that can set configuration parameters. Method see Step 3:
3)按(键或 grad\boldsymbol{\nabla} 揵对光标所在位的数字进行加或减,按 OK 键进行光标移位或确认设置参数: 3)Press the key or grad\boldsymbol{\nabla} key to add or subtract the number at the cursor position, and press OK to move the cursor or confirm the parameter setting:
4)若输入配置口令正确则进入參数设置界面(第一行为设置参数项,第二行为参数范围,第二行为当前值,第四行为设置参数值),按 /_\\boldsymbol{\triangle} 键与 grad\boldsymbol{\nabla} 键可进行参数配置项选择,选择需要配置的参数项按 OK 键,则进入当前参数项配置模式: 4)If the input configuration password is correct, it will enter the parameter setting interface (the first row is the parameter setting item, the second row is the parameter range, the third row is the current value, and the fourth row is the parameter setting value). Pressing /_\\boldsymbol{\triangle} key and grad\boldsymbol{\nabla} key can select the parameter configuration item. Select the parameter item to be configured and press OK to enter the current parameter item configuration mode:
5)按照步骤 3 对参数进行设置,若设定的数值在范同内,则该值被保存。若超出范围,则不能被保存。 5)Set the parameters according to step 3. If the set value is within the range, it will be saved. If it exceeds the range, it cannot be saved.
Q 注意:在设置过程中,任何时候按目键则立即中断当前参数设置,回到主显示界面。 Q Note: During the setting process, pressing the cursor key at any time will immediately interrupt the current parameter setting and return to the main display interface.
5.编程参数范围及定义一览表5. Overview Table of Programming Parameter Range and Definitions
序号Serial Number
功目Item
产数范围Production Range
出厂值Factory Value
描述Description
1
|j电电庆正常延时|j electrical normal delay
(0-3600)s(0 - 3600) s
10
当市电电压从不正常到正常或从正常到不正常的确认时间,用于 ATS 的切换。 The confirmation time when the city power voltage changes from abnormal to normal or from normal to abnormal, used for ATS switching.
2
|j电电压异常延时|j Voltage abnormal delay
(0-3600)s(0-3600) s
5
3
市电电压过低阈值City power voltage low threshold
(30-620)V(30-620) V
184
当乐样电压低于此值,即认为市电电压过低,当没为 30 V 时,不检测电压过低信号,回差为 10 V 。 When the load voltage is below this value, it is considered that the mains voltage is too low. When set to 30 V, the undervoltage signal is not detected, and the hysteresis is 10 V.
4
市电电压过高閾值Mains voltage overvoltage threshold
(30-620)V(30-620) \mathrm{V}
276
当采样电压高于此值,即认为市电电压过高,当设为 620 V 时,不检测电生过低信号,回差为 10 V 。 When the sampled voltage is higher than this value, it is considered that the mains voltage is too high. When set to 620 V, the undervoltage signal is not detected, and the hysteresis is 10 V.
5
开关转换间隔Switching interval
(0-99.9)s(0-99.9) s
1.0
从立电分闸到发电合闸或从发电分闸到|i 电合闻中间的间隔时间。 The interval time between the disconnection from the power supply and the connection during generation, or between the disconnection during generation and the connection to the power supply.
6
开机延时Start-up delay
(0-3600)s(0-3600) s
1
从1j电异常或远端开机信号有效到机组开机的时间。 The time from a 1j electrical abnormality or a valid remote startup signal to the startup of the unit.
7
停机延时Shutdown delay
(0-3600)s(0-3600) s
1
从市电正常或远積开机信号无效到机组停机的时间。The time from normal city power or remote start signal being ineffective to unit shutdown.
8
起动次数Number of starts
(1-10)次(1-10) times
3
发动机起动不成功时,最多起动的次数。当达到设定的起动次数时,控制器发出起动失败信号。 The maximum number of starts when the engine fails to start. When the set number of starts is reached, the controller issues a start failure signal.
9
预热时间Preheating time
(0-300)s(0-300) s
0
在起动机加电前,顶热塞顶加电的时间。The time when the top of the starter solenoid is powered on before the starter is powered on.
10
起动时间Starting time
(3-60)s(3-60) s
8
每次起动机加电的时间。Time for each starting motor to be powered on.
11
起动间隔时间Starting interval time
(3-60)s(3-60) s
10
当发动机起动不成功时,在第二次加电开始前等待的时间。 The time to wait before the second power-on attempt when the engine fails to start.
12
安全运行时间Safety operating time
(1-60)s(1-60) s
10
在此时间内油左低、水温高、久速、欠频、火长、充电失败报警量均无效 During this time, low oil pressure on the left, high water temperature, over-speed, under-frequency, long flame, and charging failure alarm quantities are all invalid.
13
开机怠速时间Idle time after startup
(0-3600)s(0-3600) s
0
开机时发电机组怠速运行的时间。The time during which the generator set idles after startup.
14
高速喥札时间High-speed shutdown time
(0-3600)s(0-3600) s
10
发电机进入高速运行后,在合闸之前所需暖机的时间。 The time required for the generator to warm up before closing the circuit after entering high-speed operation.
15
高速散热时间High-speed cooling time
(3-3600)s(3-3600) s
10
在发电机组傈载后,在停机前所需高速散热的时间。The time required for high-speed cooling after the generator set is loaded before shutdown.
16
停机怠速时间Idle time during shutdown
(0-3600)s(0-3600) s
0
停机时发电机组怠速运行的时间。The time the generator set runs in idle mode during shutdown.
17
得电停机时间Power-off time
(0-120)s(0-120) s
20
当要停机时,停机电磁铁加电的时间。The time when the power-off solenoid is energized when shutdown is required.
18
等待停稳延时Waiting for stable delay
(0-120)s
0
当"得电停机输出时间"设为 0 s 时,从㥐速延时结束到停稳所需时间;当"得电停机输出时间"不等于 0 s 时,从得电停机延时结束到停稳所需的时间。 When the "Power-on stop output time" is set to 0 s, it is the time required from the end of the acceleration delay to coming to a stop; when the "Power-on stop output time" is not equal to 0 s, it is the time required from the end of the power-on stop delay to coming to a stop.
19
开关合闸延时Switch closing delay
(0-10)s
5.0
市电合阉及发电合闻脉冲宽度,当为 0 s 时表示为持续输出。 Mains power synchronization and generator synchronization pulse width, when 0 s, indicates continuous output.
20
发动机齿数Engine tooth count
(10-300)(10-300)
118
发动机上飞轮的莢数,用于起动机分离条件的判断及发动机转速的检测 Number of flywheel pockets on the engine, used for 判断 the starting motor separation conditions and detecting engine speed
21
发电异常延时Abnormal power generation delay
(0-20.0)s(0 - 20.0) s
10.0
发电电失过高或过低报警延时。Alarm delay for excessively high or low power generation voltage.